The DaqLink Temp/RH logger is a stand-alone device with USB interface, offering rich functionality in a compact size. With built-in temperature and humidity sensors plus four external inputs each capable of measuring voltage, current, temperature, pulse and frequency, the DaqLink Temp/RH provides a cost-effective and accurate data logging solution. For continuous indoor or outdoor monitoring, the DaqLink is the tool of choice.
Key product benefits:
OUTPUTS |
|
External Power Excitation (transducers usage) |
• 12 VDC @ 300 mA • Reset fuse overload protection |
Dry Contact Alarm Output
|
• Open collector • Close position resistance: 50 Ω • Max. Load: 50 mA, 3 V DC |
LOGGER SAMPLING FEATURES |
|
|
• Memory capacity: ~59,000 samples (depending on logger configuration) • Sampling rate: One every second to one every 18 hours • Channel separation: 80 dB |
HARDWARE SPECIFICATIONS |
|
Display |
• 2-row LCD • 16 character display |
Memory Modes
|
• Cyclic/Non-cyclic • Push to Run • Pause logging |
Power Supply
|
• Internal rechargeable 4.8 V, 800 mAh NiMH battery • External 12 V DC input @ 300 mA 3.6 VA • Battery Life: Up to 10 months, depending on logger configuration |
Operating Temperature Range
|
-20 to 50 ˚C |
PC Communication
|
• USB 2.0 compliance • Mini USB type B cable |
Casing
|
• Plastic PC-ABS • Dimensions: 104 x 93 x 27 mm • Weight: 153 g • Supports table and wall mounting |
Man Machine Interface |
• Two-button keypad operation |
Standards Compliance |
• CE, FCC, IC Canada • Water and dust proof: IP54 |
INPUT TYPES |
|
4-20 mA
|
• Range: 4 to 20 mA • Resolution: 47.6 μA • Accuracy: ±0.5 % • Loop impedance: 21 Ω |
0 to 50 mV
|
• Range: 0 to 50 mV • Resolution: 37 μV • Accuracy: ±0.5 % • Input impedance: 25 MΩ • Max voltage: 3.2 V |
0 to 1 V
|
• Range: 0 to 1 V • Resolution: 200 μV • Accuracy: ±0.5 % • Input impedance: 25 MΩ • Max voltage: 3.2 V |
Temperature PT-100 (2-wires)
|
• Range: -200 to 400 ˚C • Resolution: 0.1 ˚C
• Accuracy: -60 to 60 ˚C: ±0.3 ˚C 60 to 400 ˚C: ±0.5 % |
Temperature Thermocouple J
|
• Range: -200 to 1,000 ˚C • Resolution: 0.1 ˚C
• Accuracy: -60 to 60 ˚C: ±0.5 ˚C 60 to 1,000 ˚C: ±0.5 % • Cold junction compensation error: ±0.3 ºC |
Temperature Thermocouple K
|
• Range: -200 to 1,000 ºC • Resolution: 0.1 ˚C
• Accuracy: -60 to 60 ˚C: ±0.5 ˚C 60 to 1,000 ˚C: ±0.5 % • Cold junction compensation error: ±0.3 ˚C |
Temperature Thermocouple T
|
• Range: -200 to 400 ˚C • Resolution: 0.1 ˚C
• Accuracy: -60 to 60 ˚C: ±0.5 ˚C 60 to 400 ˚C: ±0.5 % • Cold junction compensation error: ±0.3 ˚C |
Frequency (input 4 only)
|
• Range: 20 Hz to 4 KHz • Input signal: 0 to 5 V • Input impedance: 470 Ω |
Pulse Counter (input 4 only)
|
• Range: 1 to 65,536 counts • Resolution: 1 count • Frequency range: 0 to 4,000 Hz • Input signal: 0 to 3.2 V • Input impedance: 470 Ω |
Contact |
• Range: Open/Closed |
Internal Temperature
|
• Range: -20 to 50 ˚C • Accuracy: ±0.5 ˚C • Resolution: 0.1 ˚C |
Internal Humidity
|
• Range: 5 to 95 % RH • Accuracy: ±3 % at 10 to 90 % RH ±5 % at 5 to 10 % RH and 90 to 95 % RH • Resolution: 0.5 % RH |
|
• Memory capacity: ~59,000 samples (depending on logger configuration) • Sampling rate: One every second to one every 18 hours • Channel separation: 80 dB |